游艇会官网yth206

021-58765400
CN

Technical Parameters

cs1Capacity:160-16000kVA
cs2Voltage:35kV and below
cs3Voltage regulation range:No?load tap?changing: ±5%, ±2×2.5% or others; On?load tap?changing: ±4×2.5%, ±3×2.5% or others.
cs4Number of phases: 3?phase
cs5Frequency: 50?Hz or 60?Hz
cs6Vector group: Dyn11, Yyn0, Yd11, YNd11 or others
cs7Insulation class: Class F or Class H
cs8Insulation level: 1?kV class AC3, 6?kV class LI60AC20, 10?kV class LI75AC35, 20?kV class LI125AC50, 35?kV class LI170AC70
cs9Cooling method: Natural Air (AN), Natural Air (AN)/Forced Air (AF) or others
cs10Protection degree: IP00, IP20, IP23, IP24, IP30 or others
cs11Normal service conditions: Altitude not exceeding 1000?m; ambient air temperature not higher than 40?°C; minimum ambient temperature not lower than ?5?°C for indoor installation, not lower than ?30?°C for outdoor installation.

Product Features

  • An energy?saving and eco?friendly product with safety, flame?retardant performance, low noise and zero pollution, which can be installed at load centers. It is a reliable product complying with climate C2, environment E2 and fire?behaviour F1 classes.
  • High?voltage and low?voltage windings adopt full?foil construction, featuring strong resistance to lightning impulse and short?circuit as well as high operational reliability.
  • High?voltage and low?voltage windings are of full?epoxy?resin vacuum?cast construction with low partial discharge. Air ducts (patented technology) can be arranged for excellent moisture?proof and heat?dissipation performance. The transformer can run normally under 100?% relative humidity and at ?25?°C. Its capacity can be increased by 25?40?% under forced?air cooling.
  • Easy for installation and maintenance, with low operating losses and low comprehensive operating costs.
  • Equipped with temperature display and control system immune to electric and magnetic interference. A computer interface can be provided to realize remote control and monitoring, guaranteeing safe operation of the transformer.
  • It can be fitted with protective enclosure and connecting busbars, suitable for indoor or outdoor application. The indoor modular assembled enclosure is free from the limitation of door?frame dimensions at site. The connecting busbars can be directly connected to switchgear busbars for broad applicability.
td

Product Parameters

Technical Parameters and Overall Dimensions of 10?kV Class Three?Phase Resin?Insulated Dry?Type Power Transformer

Number of phases        3?phase
Frequency        50Hz
Service conditions        Normal service conditions
High?voltage        10(11、10.5、6.3、6.0)kV
HV tapping range        士5% or 士2x2.5%
Low?voltage        0.4kV
Vector group symbol           Dyn11 or Yyn0
Voltage regulation method        Off?circuit tap?changer
Insulation class           F or H
High?voltage and low?voltage windings: vacuum epoxy resin casting
byq

Drawing of Overall Dimensions and Terminals for 10?kV Class Three?Phase Resin?Insulated Dry?Type Power Transformer

SCB系列10kV,20kV及35kV级变压器柜表型尺寸图

byqg